Trade term
MPO and MTP
An MPO or MTP connector carries several fibres at once: 8 to 32, and more on some variants, aligned in one or two rows in a single ferrule. In a data centre, it is what allows dense cabling of high-speed links, where one connector per fibre would take up too much space.
MPO or MTP?
MPO (Multi-fibre Push-On) is the name of the connector interface, defined by IEC 61754-7 and, in North America, by TIA-604-5 (FOCIS 5). MTP is a registered trademark of US Conec: an MPO with better-engineered mechanics (floating ferrule, stainless steel guide pins, removable housing to change gender or inspect the ferrule), which mates with any MPO. In the field, people often use one for the other. Optical cabling and its components are covered by TIA-568.3.

What to check before patching
- Number of fibres
An MPO-12 may use only 8 (parallel links such as SR4): the unused positions stay empty. An 8-fibre connector mates mechanically with a 12-fibre one, but only the common fibres pass. MPO-16 and MPO-32 have different keying and do not mate with MPO-12 and MPO-24.
- Fibre type
Multimode OM3, OM4 or OM5, single-mode OS2: do not mix types on one link.
- Male or female
The male has two guide pins; the female has none. An adapter joins a male to a female. Two males do not mate; two females push together without alignment and give a degraded link.
- Key and adapter
The connector has a key (key up or key down). Type A adapter: key up against key down; type B: key up against key up. The choice of adapter changes the fibre mapping.
- Polarity
It says which fibre at one end arrives at which fibre at the other. Methods A, B and C of TIA-568.3 (not to be confused with type A and type B adapters) fix it for the whole link; wrong polarity gives a dead link even though everything is plugged in.
- Polish
UPC (flat face, slightly domed) or APC (face angled at 8°, mainly single-mode): do not mix them, or you risk damaging both end faces.
Inspection and cleaning: twelve fibres at once
A 12-fibre MPO ferrule means twelve end faces to keep clean, and the ferrule is wider than an LC connector. Inspection uses an inspection tip designed for MPO, against the acceptance criteria of IEC 61300-3-35; cleaning uses a tool designed for this format. An MPO connector you do not inspect is one you do not control.
Where you come across it
In rack-to-rack links (“trunk” cables), in cassettes that break an MPO out into LC connectors towards the equipment, in fan-out cords that do the same in flexible cable, and in high-speed parallel links. It is found in computer rooms as in meet-me rooms.
Content written by the Full Connection field team and approved by Karim Bouacida, head of the company.
Frequently asked questions
Can an MPO connector be mated with an MTP connector?
Yes, they are compatible: MTP is a branded MPO (US Conec) with improved mechanics. You must still match the fibre count, the male-female pairing, the adapter and the polarity.
Does an MPO-8 connector mate with an MPO-12?
Mechanically yes, they mate; only the fibres present on both sides pass. It is the MPO-16 and MPO-32 that have different keying and do not mate with MPO-12 and MPO-24.
What is the polarity of an MPO link?
It is the correspondence between the fibres at one end and those at the other. If it is wrong, transmit at one end does not arrive at receive at the other: the link does not come up.
Why inspect an MPO more carefully than an LC?
Because a single speck of dust on one of the fibres is enough to degrade the link, and the ferrule is wider and harder to clean.